Automatic Fire Sprinkler Systems - Principle of Operation

Components of an automatic fire sprinkler system

Typical Wet Pipe Fire Sprinkler SystemTypically, a Fire Sprinkler Systems are made up from a series of components including; Stop Valve, Alarm Valve, Fire Sprinkler (head), Alarm Test Valve and Motorised Alarm Bell (Gong). In addition to this there are additional components that support this arrangement including a Valve Monitor, Pressure Switch and Flow Switch.

The illustration to the right shows each of these components, and the approximate location within the arrangement.

This illustration shows only one type of fire sprinkler system however there are other types including dry pipe, pre-action, tail-end, residential and domestic fire sprinkler systems..

Purpose of each main component

(1) Stop Valve - The Stop Valve is used to isolate the water supply, it may also be called the isolating valve. It is often painted RED in colour with a large black circular handle, and is locked in the OPEN position, allowing the free flow of water. The stop valve is used to isolate (stop) the water supply coming in to the fire sprinkler system. Often the Stop Valve is also fitted with a (2) Valve Monitor that is used to monitor the state (open or closed) of the Stop Valve.

The water within an automatic fire sprinkler system can be divided into two parts;

  • Water Supply or Mains; and
    This is the water being fed into an automatic fire sprinkler system from a water supply such as the town mains or a static water supply such as a tank, up to the Stop Valve
  • Installation
    The water after the stop valve forms part of the installation.

(3) Alarm Valve - The Alarm Valve is used to control the flow of water into the fire sprinkler system. This is accomplished by providing a one way valve that is normally closed when the water pressure on the fire sprinkler side of the valve exceeds the water supply pressure. When the pressure equalises or falls below the water supply pressure, the valve opens to enable water flow.

(4) Automatic Fire Sprinkler - The Fire Sprinkler is also used to control the flow of water. It is essentially a valve that when exposed for a sufficient time to a temperature at or above the temperature rating of the heat sensitive element (glass bulb or fusible link) releases, allowing water to flow from only the affected sprinkler. The operation and subsequent water flow of an automatic fire sprinkler will lead to a drop in pressure within the fire sprinkler system after the alarm valve.1

(5) Alarm Test Valve - The alarm test valve is a small valve, normally secured in the closed position. The alarm test valve is fitted between the sprinkler system side of the alarm valve and the drain. The purpose of the alarm valve is when opened to simulate the flow of water from a single automatic fire sprinkler.

(6) Motorised Alarm Bell or Gong - The motorised alarm bell or gong is a mechanical device, operated by the flow of water oscillating a hammer that strikes a gong, causing an audible alarm signal.

Ancillary Components

In addition to the main components of the fire sprinkler system, there are a series of ancillary (support) components that regularly form part of an automatic fire sprinkler system.

(7) Pressure Switch - The pressure switch is an electro-mechanical device that monitors a fire sprinkler system for a fall in water pressure after the alarm valve. The purpose of monitoring a fall in pressure is to activate a switch that is monitored by a fire alarm panel or alarm signalling equipment, as the primary method for signalling an alarm to the fire brigade.

(8) Flow Switch - The flow switch is an electro-mechanical device that monitors the flow of water through a section of pipe within an automatic fire sprinkler system. Flow switches are often fitted with a mechanical delay (up to six minutes) preventing small or minor water flow fluctuations from signalling an alarm. When sustained water flow is detected by a flow switch, a signal is transmitted to a fire indicator panel. This signal is then used to determine which section (floor) of a fire sprinkler system has water flow. Note: Most flow switches fitted to automatic fire sprinkler systems are NOT set to automatically call the fire brigade

(9) Jacking Pump - Jacking are manual (hand) or electric (semi-automatic or fully automatic) pumps are not always fitted to an automatic fire sprinkler system. They however provide a method of pumping (boosting) water from the water supply to the fire sprinkler system after the alarm valve. This leads to an increase in water pressure in the fire sprinkler system, thus forcing the alarm valve into the closed position. Jacking Pumps have a secondary function of maintaining the water pressure within a fire sprinkler system reducing the likelihood of false alarms caused by low pressure, caused by small water leaks.

Pressure Gauge - A pressure gauge us a mechanical device that is usually fitted to an automatic fire sprinkler system. There are usually two gauges fitted to a system, one showing the water supply pressure and the second showing the installation pressure. Normally the pressure differential should be not less than 200 KPa.

Principle of operation

Normally an wet pipe automatic fire sprinkler system, is fully charged with water coming from a known reliable water supply. The installation is pressurised with the alarm valve secured in the open position. When a fire sprinkler is exposed for a sufficient time to a temperature at or above the temperature rating of the heat sensitive element (glass bulb or fusible link) it releases, allowing water to flow from only the affected sprinkler. Additional fire sprinklers may also operate if they too are exposed to sufficient heat.

When this occurs water from the water supply will pass through the alarm valve to the affected fire sprinkler and also past the alarm bell. The resultant pressure drop will also activate the alarm pressure switch, which in turn will activate an alarm calling the fire brigade.

A flow switch will also operate in the affected section of the fire sprinkler system, indicating the location of the water flow. (In the case of a multi-storey building there is typically one flow switch per floor). The flow switch will indicate its location a fire indicator panel (but may not call the fire brigade).

The water supply may be isolated (stopping the flow of water to the affected fire sprinklers) by closing the stop valve.

Summary and other resources

As an active contributor to Wikipedia, I must say there are some great resources on Active Fire Protection, Fire Sprinklers and Fire Sprinkler Systems. You can also search this web site for more information.

More articles in this series

About the author

Russ Porteous is the CEO and one of the founders of Maintenance Essentials, he has over 22 years experience in the installation and maintenance of fire and essential safety measures. Russ is an active contributor to a variety of Australian Standards including AS1851 for the Maintenance of Fire Protection Systems and Equipment. Russ speaks regularly at conferences and trade shows as a subject matter expert. You can follow Russ online via Twitter @rport or his popular fire safety blog.

4.255815
Average: 4.3 (43 votes)
Your rating: None

Comments

 
Why are "control valves" a fire safety matter under Bldg Regs?
Submitted by dswinson on June 26, 2010 - 13:14.

This is a great post Russell. One of the best explanations I have seen of the operation of a sprinkler system. On a more specific issue to do with sprinklers, Joe Zita from Approval Systems raised a really interesting question about "control valves" or alarm valves as you refer to them above. They are listed as a Regulation 309 fire safety matter for variations to the Building Regulations. They are the only part of a sprinkler system to be included in this way.

We have done a blog post at www.buildingregulations.com.au on this issue.

We propose to do a post on The Building Regulations Blog just linking to your Principle of Operation post. It's a really great piece of work!

Keep up the good work Russell!

David Swinson,
BDC Building Design Compliance Pty Ltd
http://www.bdcompliance.com.au

 
Thanks a lot for the info
Submitted by mayur kadam (not verified) on May 27, 2012 - 16:05.

Thanks a lot for the info

 
Reply to comment | Firewize
Submitted by Seo Dienstleistungen (not verified) on September 27, 2012 - 01:28.

WOW just what I was searching for. Came here by
searching for totally

 
anti tamper monitors
Submitted by steve hart (not verified) on November 22, 2012 - 20:37.

Hi just wondered if you could inform me on the selection of class A anti tamper monitors in the market place. Do they all comply with the relevant Australian standard? Are all of these devices imported from overseas? Is it mandatory to have such a device in all systems. From a maintenance prospective what does the australian standard say as to how often these devices should be tested.

regards steve

 
good article. i was amaze
Submitted by Brandy Espinoza (not verified) on January 10, 2013 - 10:54.

good article. i was amaze about different components of fire sprinklers. It show how it works

 
Excellent Post
Submitted by Jason Hugo (not verified) on February 27, 2013 - 00:53.

A little late to the comments here, but excellent and very well laid out post. Our company distributes fire sprinkler system components to contractors and plumbers in the states. It's nice to see such a well written yet digestible piece of literature explaining a fire sprinkler system and it's components.

Thank you,

Jason Hugo

QRFS, LLC
http://qrfs.com